Generator Model | GJP900-ST | |
Standby | kVA | 900 |
kW | 720 | |
Prime | kVA | 800 |
kW | 640 | |
Engine Speed | r.p.m | 1500 |
Voltage | V | 230/400 |
Power Factor | Cos Phi | 0,8 |
Model | 4006-23TAG3A | |
Net Motor Output Power | kW | 675 |
Standby Output Power | kW | 756 |
Brand | Perkins | |
Engine Type | 4 Stroke - Diesel | |
Spray Type | Direct Injection | |
Suction Type | Turbo Charge & Aftercooler | |
Number of Cylinders | 6 | |
Bore and Stroke | mm | 160 x 190 |
Cylinder Volume | L | 22,9 |
Cooling Type | Water Cooled | |
Compression Ratio | 13.6:1 | |
Fuel Consumption at Stand by Load | l/h | 194 |
100% Prime Load Fuel Consumption | l/h | 172 |
75% Fuel Consumption at Prime Load | l/h | 137 |
50% Fuel Consumption at Prime Load | l/h | 130 |
Total Oil Capacity | L | 113,4 |
Total Cooling Capacity | L | 170 |
Governor Type | Type | Electronics |
Model | HCI634G | |
Brand | Stamford | |
Output Voltage | V | 230/400 |
Frequency | HZ | 50 |
Automatic Voltage Regulation | ±% | 1 |
Alternator Prime Power | kVA | 810 |
Power Factor | Cosq | 0,8 |
Number of Cables | 12 | |
Winding Pitch | 2/3 | |
Protection Class | IP23/H | |
Warning System | Self-excited | |
AVR Model | MX321 | |
Performance - PF 0.8 / 75% Load | % | 95,2 |
Dimensions (Open Set) | ||
LxWxH | mm | 4600x2100x2570 |
Weight | kg | 7743 |
Fuel Tank | lt | 1490 |
Dimensions (With Cabin) | ||
LxWxH | mm | 5450x2100x3330 |
Weight | kg | 8100 |
Fuel Tank | lt | 1490 |
Related products
Stamford
Stamford
Stamford
Stamford
Stamford
Stamford
Stamford
Stamford