Model | GJC33-ST | |
Standby | kVA | 33 |
Standby | kW | 26,4 |
Prime | kVA | 30 |
Prime | kW | 24 |
Engine Speed | r.p.m | 1500 |
Voltage | V | 230/400 |
Power Factor | Cos Phi | 0,8 |
Model | X2.7TAA-G2 | |
Brand | CUMMINS | |
Engine Type | 4 Stroke - Diesel | |
Spray Type | Direct Injection | |
Emme Sistemi | Natural | |
Number of Cylinders | 3 | |
Bore and Stroke | mm | 91,4x127 |
Cylinder Volume | L | 3,3 |
Cooling Type | Water Cooled | |
Fuel Consumption at Stand by Load | l/h | 10,4 |
100% Prime Load Fuel Consumption | l/h | 8,5 |
75% Fuel Consumption at Prime Load | l/h | 6,1 |
50% Fuel Consumption at Prime Load | l/h | 4,3 |
Total Oil Capacity | L | 6,5 |
Total Cooling Capacity | L | 8,6 |
Governor Type | Type | Electronics |
Model | SOL2-P1 | |
Brand | STAMFORD | |
Output Voltage | V | 230/400 |
Frequency | HZ | 50 |
Automatic Voltage Regulation | ±% | 1 |
Alternator Prime Power | kVA | 45 |
Power Factor | Cosq | 0,8 |
Number of Cables | 12 | |
Winding Pitch | 2/3 | |
Protection Class | IP23/H | |
Warning System | Self-excited | |
AVR Model | TBD | |
Performance - PF 0.8 / 75% Load | % | 89,3 |
Dimensions (Open Set) | ||
LxWxH | mm | 1770x850x1440 |
Weight | kg | 1160 |
Fuel Tank | lt | 135 |
Dimensions (With Cabin) | ||
LxWxH | mm | 2225x950x1660 |
Weight | kg | 1220 |
Fuel Tank | lt | 135 |
Related products
Stamford
Stamford
Stamford
Stamford
Stamford
Stamford
Stamford
Stamford