Generator Model | GJP72-ST | |
Standby | kVA | 72 |
kW | 57,6 | |
Prime | kVA | 65 |
kW | 52 | |
Engine Speed | r.p.m | 1500 |
Voltage | V | 230/400 |
Power Factor | Cos Phi | 0,8 |
Model | 1104A-44TG1 | |
Net Motor Output Power | kW | 58 |
Standby Output Power | kW | 64 |
Brand | Perkins | |
Engine Type | 4 Stroke - Diesel | |
Spray Type | Direct Injection | |
Suction Type | Turbo Charge | |
Number of Cylinders | 4 | |
Bore and Stroke | mm | 105 x 127 |
Cylinder Volume | L | 4,4 |
Cooling Type | Water Cooled | |
Compression Ratio | 17.25:1 | |
Fuel Consumption at Stand by Load | l/h | 16,2 |
100% Prime Load Fuel Consumption | l/h | 14,8 |
75% Fuel Consumption at Prime Load | l/h | 11,2 |
50% Fuel Consumption at Prime Load | l/h | 8 |
Total Oil Capacity | L | 8 |
Total Cooling Capacity | L | 13 |
Governor Type | Type | Electronics |
Model | UCI224F | |
Brand | Stamford | |
Output Voltage | V | 230/400 |
Frequency | HZ | 50 |
Automatic Voltage Regulation | ±% | 1 |
Alternator Prime Power | kVA | 72,5 |
Power Factor | Cosq | 0,8 |
Number of Cables | 12 | |
Winding Pitch | 2/3 | |
Protection Class | IP23/H | |
Warning System | Self-excited | |
AVR Model | AS440/SX460 | |
Performance - PF 0.8 / 75% Load | % | 90,7 |
Dimensions (Open Set) | ||
LxWxH | mm | 1900x900x1610 |
Weight | kg | 1020 |
Fuel Tank | lt | 220 |
Dimensions (With Cabin) | ||
LxWxH | mm | 2440x1000x1860 |
Weight | kg | 1440 |
Fuel Tank | lt | 220 |