Generator Model | GJY250-NG | |
Gas Source | Natural Gas | |
Standby kVA | 350 | |
Prime kVA | 312,5 | |
Standby kW | 280 | |
Prime kW | 250 | |
Rpm | (r/min) | 1500 |
Voltage Options | V | 400 |
Frequency | 50 | |
Power Factor | 0,8 | |
Electricity Efficiency | % | ≥38 |
Thermal Efficiency | % | ≥54.1 |
Total Productivity | % | ≥92.1 |
Gas Consumption | m³/h | 72,3 |
Heat balance parameters | ||
Coolant temperature of cylinder liner (±8%) | kW | 192 |
Coolant temperature of the oil cooler (±%8) | kW | 44 |
Total cooling water temperature of the high temperature cooling system (± %8) | kW | 236 |
Coolant temperature of the intercooler (±%8) | kW | 45 |
Total coolant temperature of the low temperature cooling system (± 8) | kW | 45 |
Exhaust gas waste heat (exhaust gas temperature up to 120°C’) (±%8) | kW | 136 |
Total radiant heat (±%8) | kW | 25 |
Cooling parameters | ||
Yüksek sıcaklıktaki sirkülasyon suyunun akış hızı | m³/h | 9,2 |
Inlet temperature of high temperature circulating water (± %2) | °C | 78,9 |
Outlet temperature of high temperature circulating water (± %2) | °C | 85 |
Low temperature inlet water temperature (±%2) | °C | 50 |
Low temperature inlet water temperature (±%2) | °C | 52 |
Intake and exhaust parameters | ||
Air intake | kg/h | 1243 |
Gas input | kg/h | 51 |
Air displacement | kg/h | 1294 |
Exhaust temperature after turbocharging (±%5) | °C | 490 |
Test Conditions | ||
Calorific value of gas | kWh/m | 9,1 |
Methane volume content | % | ≥96 |
Gas temperature | °C | -10~40°C |
Gas inlet pressure(Before regulator) | kPa | 800~1000 |
Gas inlet pressure(After regulator) | kPa | 400~600 |
Air intake negative pressure | kPa | >-3 |
Exhaust back pressure | kPa | <5 |
Absolute atmospheric pressure | kPa | 101,32 |
Ambient temperature | °C | 25 |
Relative humidity | % | 30 |
Height | m | ≤1,000 |